Sec. 09.12.01.02. Access and Egress  


Latest version.
  • A. Clearance.

    (1) Except for a water heater or a modular boiler system, a new or replacement boiler installed in a new or existing building shall be installed consistent with:

    (a) Or exceeding, the manufacturer's recommendations for clearance; and

    (b) The space requirements of §A(6) of this regulation.

    (2) In the event manufacturer recommendations for clearance are not provided, a new or replacement boiler installed in a new or existing building, shall:

    (a) Have at least 3 feet between:

    (i) The top of the boiler and the ceiling, and

    (ii) Each side of the boiler and the adjacent wall or other structure; and

    (b) Comply with the conditions of §A(6) of this regulation.

    (3) The distance between or around a new or replacement boiler in a modular boiler system installed in a new or existing building shall be in accordance with the manufacturer's recommendations while ensuring:

    (a) There are 3 feet between each side of the perimeter of the boiler system and the adjacent wall or structure; and

    (b) The conditions in §A(6) of this regulation are met.

    (4) The distance between or around a water heater installed in a new or existing building shall be in accordance with the manufacturer's recommendations while ensuring the conditions of §A(6) of this regulation are met.

    (5) A boiler or pressure vessel having a manhole shall have 5 feet clearance from the manhole opening to any wall, ceiling, or piping that prevents entrance through the manhole.

    (6) A boiler or pressure vessel shall be located to provide adequate space for:

    (a) Proper operation of the boiler or pressure vessel and its appurtenances;

    (b) Inspection of all surfaces, tubes, water-walls, economizers, piping, valves, and other equipment; and

    (c) Required maintenance and the repair and replacement of tubes.

    B. Ladders and Runways.

    (1) When necessary to afford safe access, a steel runway or platform of standard construction shall be installed across the tops of adjacent boilers or pressure vessels, or at another convenient level.

    (2) When a valve or appurtenance requiring frequent manipulation cannot be reached or operated from the floor, a platform or other safe means of operation shall be provided.

    (3) A platform or runway shall:

    (a) Be at least 24 inches wide;

    (b) Have standard handrails and toe boards; and

    (c) Provide at least 7 feet, 6 inches overhead clearance.

    (4) A runway shall:

    (a) Have at least two means of exit, located remotely from each other; and

    (b) Be connected to floor level by:

    (i) A permanent stairway, or

    (ii) An inclined ladder.

    C. Each elevation in a boiler room shall have at least two exits, located remotely from each other, if the room:

    (1) Exceeds 500 square feet floor area; and

    (2) Contains one or more boilers having a fuel-burning capacity of 1,000,000 Btu per hour, or equivalent electrical heat input.